70
Electrical installation
Type 8098 FLOWave L
8.17
Specifications of the cables and conductors for the
4-pin M12 female connectors
Table 19:
Specifications of the cables and conductors for the 4-pin M12 female connectors
Specification of the cables and conductors
Recommended value
Electromagnetic protection (EMC)
Shielded conductor with minimum STP
Minimum category
CAT-5
Maximum length
100 m
Maximum operating temperature
80 °C or higher
8.18
Connecting the device to an Ethernet network
(device variant with two 4-pin M12 female connectors
– Ethernet device variant)
The two 4-pin M12 female connectors (D-coding) are used to connect the device to an Ethernet network.
Risk of damage to the device if any M12 connector is unused.
▶
Put a screwed plug on all the unused M12 connectors. Screw the plug of the 4-pin M12 female
connector to a torque of 1.3 Nm (0.96 ft·lbf).
If a device with two 4-pin M12 female connectors (Ethernet device variant) is connected to an Eth
-
ernet network, you must connect it to a büS / CANopen network for the configuration of the device
with the software Bürkert Communicator.
If a device is connected to an Ethernet network, the measured process values are transmitted via the Eth-
ernet network.
Each 4-pin M12 female connector (D-coding) has the same pin assignment: See Fig. 36
.
1
2
3
4
•
Pin 1: Tr
•
Pin 2: R
•
Pin 3: Transmit –
•
Pin 4: Receive –
Fig. 36:
Pin assignment of the 4-pin M12 female connector
→
Loosen the screwed plug of the 4-pin M12 female connector and store the screwed plug in a safe and
clean place.
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...