General settings – Parameter
Type 8098 FLOWave L
→
OK
→
Save the name.
The unique name is set.
12.6.2
Changing the transmission speed on the device
The transmission speed for the communication on the fieldbus (both büS or CANopen) must be the same
for all the participants of the fieldbus.
By default, the transmission speed of the device is 500 kbit/s. This transmission speed is suited for a
maximum cable length of 50 m.
If the cable length is higher, reduce the transmission speed of all the participants.
To change the transmission speed of the device, do the following:
→
Go to the
CONFIGURATION
view.
→
General settings
→
Confirm to access the
Parameter
view.
→
büS
→
Advanced
→
Baudrate
→
Choose the transmission speed.
→
Save.
The transmission speed of the device is changed. To take the transmission speed into account, restart
the device.
12.6.3
Activating the device internal termination resistor
If the device is connected to a CANopen fieldbus or to büS, a 120
W
termination resistor must be installed
at each end of the fieldbus or of büS.
To avoid installing a physical termination resistor, the device has an internal 120
W
termination resistor that
can be activated if the device is installed at one end of the büS network or at one end of the CANopen
network.
• If you activate the device internal termination resistor, do not install a termination resistor at the
same end of büS or of the CANopen fieldbus.
•
Max. two 120
W
termination resistors can equip büS or a CANopen fieldbus.
To activate the device internal termination resistor, do the following:
→
Go to the
CONFIGURATION
view.
→
General settings
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...