166
SAW sensor – Parameter
Type 8098 FLOWave L
15.5.4
Deactivating the damping of the mass flow rate values
If the damping of the mass flow rate values is active, do the following to deactivate it:
→
Go to the
CONFIGURATION
view.
→
SAW sensor
→
Confirm to access the
Parameter
view.
→
Stand. meas. values
→
Mass flow
.
→
Damping
The
Current settings
are displayed
→
Choose
None
The
New settings
are displayed.
→
Save.
The damping of the mass flow rate values is inactive.
15.5.5
Activating the monitoring of the mass flow rate
Because of a malfunction in the process or in the mass flow rate sensor, the measured mass flow rate value
can be too high or too low.
A monitored value can be:
• in the normal operating range.
• in the warning range,
• in the error range.
You can set 4 limit values: 2 error limits and 2 warning limits.
→
To set the limit values, see chapter 15.5.7 Changing the error limits, the warning limits and the hysteresis
.
Fig. 55 explains how the device reacts when the monitored value enters in another range (for example, from
the normal range into the warning range). The reaction time depends on the hysteresis value and whether
the monitored value increases or decreases.
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...