167
SAW sensor – Parameter
Type 8098 FLOWave L
increasing
monitored
value
decreasing
monitored
value
A:
Error low
D:
Error high
C:
Warning high
B:
Warning low
A
B
C
D
1
2a
2b
3a
3b
h
h
h
h
C
D
1
2b
3b
2a
3a
A
B
2b
3b
1
2a
3a
h: value of the hysteresis. An hys-
teresis value that is equal to 0
means that the device reacts as
soon as a limit is reached.
A: low error limit (
Error low
)
B: low warning limit (
Warning low
)
C: high warning limit (
Warning
high
)
D: high error limit (
Error high
)
1: normal range of the monitored
value
2a: lower warning range of the
monitored value
3a: lower error range of the moni-
tored value
2b: upper warning range of the
monitored value
3b: upper error range of the moni-
tored value
Monitored
value is in the
Colour of the device status indicator
and generated message
Condition
Error range
Red
1)
indicator,
Failure
message
•
if the monitored value was in the LOWER
warning range and the LOW ERROR value is
reached.
• if the monitored value was in the UPPER
warning range and the HIGH ERROR value is
reached.
Warning range
Yellow
1)
indicator,
Out of specification
message
•
if the monitored value was in the LOWER error
range and the LOW ERROR value + the HYS
-
TERESIS value is reached.
• if the monitored value was in the normal range
and the HIGH WARNING value is reached.
• if the monitored value was in the UPPER error
range and the HIGH ERROR value minus the
HYSTERESIS value is reached.
• if the monitored value was in the normal range
and the LOW WARNING value is reached.
Normal range
• White
1)
indicator, no message, if
the
Diagnostics
in the menu
SAW
sensor
–
Parameter
is inactive
(default setting).
• or green
1)
indicator, no message, if
the
Diagnostics
in the menu
General
settings
–
DIAGNOSTICS
are active.
•
if the monitored value was in the LOWER
warning range and the LOW WARNING value +
the HYSTERESIS value is reached.
• if the monitored value was in the UPPER
WARNING range and the HIGH WARNING
value minus the HYSTERESIS value is reached.
Fig. 55:
Operating principle of the monitoring with an hysteresis
1)
If the operating mode of the device status indicator is set to NAMUR. See chapter 12.4
.
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...