63
Electrical installation
Type 8098 FLOWave L
8.11
Wiring the device through the M20x1.5 cable glands in
nickel plated brass (device variant with cable glands)
Put only one cable in each cable gland.
→
Prepare cables that obey the specifications given
in chapter 8.6 and chapter 8.7
.
→
To open the front of the transmitter, follow the
instructions given in chapter
1. Use a size 10 hexagonal key to loosen the 2
screws of the functional earth plate.
2 screws
2.
Strip 100 mm of the cable.
3.
Reduce the shield to 20 mm.
4.
Expose 8 mm of the conductors.
20 mm
100 mm ±5
8 mm
5. Loosen the nut of the cable gland.
6.
Remove the blind plug of the cable gland and
store the blind plug in a safe and clean place.
7. If the cable diameter is between 5 and 9 mm, put
the cable through the cable gland as shown in
the figure.
8.
Use a size 24 hexagonal key to tighten the cable
gland to a torque of 10 Nm (7.4 ft·lbf).
9.
If the cable diameter is between 9 and 14 mm,
→
vertically put a screwdriver between the two
seals,
→
lift the inner seal and remove it.
→
Put the cable through the cable gland.
→
Use a size 24 hexagonal key to tighten the cable
gland to a torque of 10 Nm (7.4 ft·lbf).
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...