46
Installation in the pipe
Type 8098 FLOWave L
7.4
Recommendations for the installation into the pipe
The device can be installed into either horizontal, oblique or vertical pipes. But an installation on a vertical
pipe is better to prevent air bubbles or gas bubbles to remain in the sensor measurement-tube.
In any case and according to the device variant, make sure to respect the following recommendations:
→
Protect this device against electromagnetic interference, ultraviolet rays and, when installed outdoors,
the effects of climatic conditions.
→
If the mass of the device could kink the pipe, install adapted pipe supports before mounting the device
in the pipe.
→
Always install a heavy device with the help of another person and with the use of appropriate tools.
→
If the liquid temperature is subject to variations, make sure that the device can expand freely.
→
Make sure the DN of the measurement tube is suited to the flow velocity: refer to the data sheet of the
The device is not intended to measure the flow rate of liquids if gas bubbles are present, whatever
the origin of the bubbles (air intake, cavitation, degassing …).
→
Choose a location with enough free space to put the magnetic key on the symbol at the side of the device.
→
Install the device upstream a valve or any equipment that changes the pipe diameter or the pipe
direction.
→
If you cannot install the device upstream a valve or any equipment that changes the pipe diameter or the
pipe direction, observe the straight downstream distances depending on the design of the pipes. Refer
to standard ISO 9104:1991 and Fig. 14
. If these recommendations cannot be complied with, contact
Bürkert.
IF YOU CANNOT INSTALL THE DEVICE UPSTREAM A VALVE OR ANY EQUIPMENT THAT CHANGES
THE PIPE DIAMETER OR THE PIPE DIRECTION, THEN OBSERVE THE FOLLOWING DISTANCES
Flow direction
Control valve
2 x 90°
elbow joint, 3
dimensional
2 x 90° elbow
joint
90° elbow joint
or T-piece
40 x DN
1 x DN
40 x DN
1 x DN
60 x DN
1 x DN
50 x DN
1 x DN
Fig. 14:
Upstream and downstream straight distances for special pipe designs (example for a horizontal
installation)
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...