X20 system modules • Compact CPUs System modules • X20PS9502
640
X20 system User's Manual 3.10
Product ID
X20PS9502
Power consumption
2)
Bus
1.44 W
Internal I/O
0.6 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
CPU/X2X Link feed - CPU/X2X Link supply
No
I/O feed - I/O supply
No
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
CPU / X2X Link supply input
Input voltage
24 VDC -15% / +20%
Input current
Max. 0.7 A
Fuse
Integrated, cannot be replaced
Reverse polarity protection
Yes
CPU / X2X Link supply output
Nominal output power
Horizontal installation
7.0 W at 45°C and 5.0 W at 55°C
Vertical installation
7.0 W at 40°C and 5.0 W at 50°C
Parallel operation
No
Redundant operation
No
Overload behavior
Short circuit / temporary overload protection
Input I/O supply
Input voltage
24 VDC -15% / +20%
Fuse
Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection
No
Output I/O supply
Rated output voltage
24 VDC
Behavior if a short circuit occurs
Required line fuse
Permitted contact load
10.0 A
Interfaces
IF1 interface
Signal
RS232
Design
Connection made using 12-pin X20TB12 terminal block
Transfer rate
Max. 115.2 kbit/s
IF3 interface
1)
Signal
CAN bus
Design
Connection made using 12-pin X20TB12 terminal block
Transfer rate
Max. 1 Mbit/s
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Protection in accordance with EN 60529
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BB22 or X20BB27 compact CPU base separately
Order 1x X20BB32 or X20BB37 fieldbus CPU base separately
Spacing
12.5
+0.2
mm
Table 221: X20PS9502 - Technical data
1)
CAN bus only when used with the X20BB27 or X20BB37 bus module.
2)
The specified values are maximum values. The calculation is also available for download as a data sheet with the other module documentation on the B&R
homepage.