X20 system modules • Digital output modules • X20DO4332
1142
X20 system User's Manual 3.10
4.15.11.9 Switching inductive loads (Rev. H0 and higher)
Environmental temperature: 50°C, all outputs with the same load.
0.1
1
10
100
Coil resistance
[Ω]
Coil inductance
10 mH
100 mH
1 H
10 H
100 H
10
100
500
Max. switching cycles / second
(with 90% duty cycle)
28.8 V
24.0 V
Switching voltage:
Environmental temperature: 60°C, all outputs with the same load.
28.8 V
24.0 V
Switching voltage:
0.1
1
10
100
Coil resistance
[Ω]
Coil inductance
10 mH
100 mH
1 H
10 H
100 H
10
100
500
max. Schaltspiele / Sekunde
(with 90% duty cycle)
Information:
If the maximum number of operating cycles per second is exceeded, an external inverse diode must
be used.
Operating conditions outside of the area in the diagram are not permitted!