X20 system modules • Analog input modules • X20AP31x1
340
X20 system User's Manual 3.10
4.3.14.10.10 Analog energy registers
4.3.14.10.10.1 Read timestamp for energy registers (+0x0022 = 16 bit)
Name:
SampleTime02_32bit
Network timestamp for the readout of the energy register.
Data type
Value
Information
DINT
-2,147,483,647 to 2,147,483,647
Network time
4.3.14.10.10.2 Forward total active energy
Name:
APenergyT
Total active energy in forward direction.
Data type
Value
Information
UDINT
0 to 4,294,967,295
Resolution 0.1 or 0.01 CF, depending on the Power Line factor (e.g. kWs)
Comments:
•
The unit CF is derived from the Power Line factor (default: 3600 Imp/kWh), see register "MeteringMode"
•
The resolution can be switched between 0.1 and 0.01, see register "MeteringMode"
•
The register is updated automatically after being enabled, see register "ControlOutput" <Bit 1>
•
The register is cleared upon request, see register "ControlOutput"
•
The register is set upon request, see register "ControlOutput" <Bit 3>
4.3.14.10.10.3 Forward active energy on phase A/B/C
Name:
APenergyA
APenergyB
APenergyC
Active energy in forward direction of the phase.
Data type
Value
Information
UDINT
0 to 4,294,967,295
Resolution 0.1 or 0.01 CF, depending on the Power Line factor (e.g. kWs)
Comments:
•
The unit CF is derived from the Power Line factor (default: 3600 Imp/kWh), see register "MeteringMode"
•
The resolution can be switched between 0.1 and 0.01, see register "MeteringMode"
•
The register is updated automatically after being enabled, see register "ControlOutput" <Bit 1>
•
The register is cleared upon request, see register "ControlOutput"
•
The register is set upon request, see register "ControlOutput" <Bit 3>
4.3.14.10.10.4 Reverse total active energy
Name:
ANenergyT
Total active energy in reverse direction.
Data type
Value
Information
UDINT
0 to 4,294,967,295
Resolution 0.1 or 0.01 CF, depending on the Power Line factor (e.g. kWs)
Comments:
•
The unit CF is derived from the Power Line factor (default: 3600 Imp/kWh), see register "MeteringMode"
•
The resolution can be switched between 0.1 and 0.01, see register "MeteringMode"
•
The register is updated automatically after being enabled, see register "ControlOutput" <Bit 1>
•
The register is cleared upon request, see register "ControlOutput"
•
The register is set upon request, see register "ControlOutput" <Bit 3>