X20 system modules • Other functions • X20CM4810
X20 system User's Manual 3.10
2075
4.26.2.2.11 Characteristic value format
Characteristic value
Format
Unit
REAL
Hz
REAL
mg or 1 when crest
REAL
mg
REAL
mg
CrestFactorHighFrequency01-04
1)
REAL
1
Vdi3832KtHighFrequency01-04
1)
REAL
1
REAL
mg
REAL
mm/s
REAL
mg
REAL
mm/s
REAL
mg
REAL
mg
REAL
1
REAL
1
REAL
1
Vdi3832KtRaw01-04
1)
REAL
1
REAL
mm/s
REAL
mg or mm/s depending on the configuration
Table 724: Characteristic values after preparation by Automation Runtime in the standard function model
1)
Additional characteristic value provided by Automation Runtime.
Characteristic value
Format
Resolution and unit
Value on overflow
UINT
0.01 Hz
INT
AnalogInputScale/32768
32767 or -32768 (cap)
24-bit unsigned
1/65536 g
16777215
24-bit unsigned
1/65536 g
16777215
24-bit unsigned
0.001 g
16777215
24-bit unsigned
0.001 mm/s
16777215
24-bit unsigned
0.001 g
16777215
24-bit unsigned
0.001 mm/s
16777215
24-bit unsigned
1/65536 g
16777215
24-bit unsigned
1/65536 g
16777215
24-bit unsigned
0.001
16777215
24-bit signed
0.001
8388607
24-bit signed
0.001
8388607
24-bit unsigned
0.001 mm/s
16777215
(configured as RMS)
24-bit unsigned
0.001 g or 0.001 mm/s
depending on the configuration
16777215
(configured as noise)
24-bit unsigned
1/65536 g or 1/65536 mm/s
depending on the configuration
16777215
Table 725: X20CM4810 characteristic values
4.26.2.3 General information about the module
4.26.2.3.1 X20CM4810 settling time
The input high-pass cut-off frequency of the AC voltage input (limit frequency of 34 MHz) means that a certain
amount of settling time is required after changing the DC offset of the pending signal.
•
Settling time of approximately 30 seconds at 100 mV/g sensor sensitivity and a 24 V supply voltage with
an accuracy of 0.4 g
•
Settling time of approximately 60 seconds at 100 mV/g sensor sensitivity and a 24 V supply voltage with
an accuracy of 0.001 g
•
The respective settling time must be allowed to pass in order to achieve accurate measurement results
when an open line occurs. Because of this, all characteristic values and analog input values are set to 0
by the module during the first 30 seconds after a restart or wire breakage.
4.26.2.3.2 Sensor sensitivity
The X20CM4810 always assumes a 100 mV/g acceleration sensor on the input. When using Function model 0 -
Standard, it is possible to configure a different sensor sensitivity directly in the function library.
If a different function model is used, for example an SGC controller or bus coupler, any conversion to a different
sensitivity must be performed manually.
Example
Summary of Contents for X20 System
Page 2: ......