X20 system modules • Analog input modules • X20AI2322
168
X20 system User's Manual 3.10
Product ID
X20AI2322
Output of the digital value during overload
Below lower limit
0x0000
Above upper limit
0x7FFF
Conversion procedure
SAR
Input filter
3rd-order low pass / cutoff frequency 1 kHz
Max. error at 25°C
Gain
0 to 20 mA
0.08%
1)
4 to 20 mA
0.1%
1)
Offset
0 to 20 mA
0.03%
2)
4 to 20 mA
0.16%
2)
Max. gain drift
0 to 20 mA
0.009 %/°C
1)
4 to 20 mA
0.0113 %/°C
1)
Max. offset drift
0 to 20 mA
0.004 %/°C
2)
4 to 20 mA
0.005 %/°C
2)
Common-mode rejection
DC
70 dB
50 Hz
70 dB
Common-mode range
±12 V
Crosstalk between channels
-70 dB
Non-linearity
<0.05%
2)
Isolation voltage between channel and bus
500 V
eff
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB06 or X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 36: X20AI2322 - Technical data
1)
Based on the current measured value.
2)
Based on the 20 mA measurement range.
4.3.5.4 LED status indicators
Figure
LED
Color
Status
Description
Off
No power to module
Single flash
RESET mode
Blinking
PREOPERATIONAL mode
r
Green
On
RUN mode
Off
No power to module or everything OK
e
Red
On
Error or reset status
e + r
Red on / Green single flash
Invalid firmware
Blinking
Input signal overflow or underflow
1 - 2
Green
On
Analog/digital converter running, value OK
Table 37: LED status indicators