X20 system modules • Other functions • X20PD0016
X20 system User's Manual 3.10
2317
4.26.8.3 Technical data
Product ID
X20PD0016
Short description
Potential distributor module
5x 24 VDC on the terminal connections, 5x ground on the terminal connections
General information
B&R ID code
0x2680
Status indicators
Operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Fuse monitoring
Yes, using status LED and software
Power consumption
1)
Bus
0.12 W
Internal I/O
-
External I/O
1.15 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Input supply
Nominal input voltage
24 VDC -15% / +20% external, external ground
Fuse
Integrated 6.3 A, slow-blow, can be replaced
Reverse polarity protection
No
Output supply
Rated output voltage
24 VDC, ground
Permitted contact load
10 A
Behavior if a short circuit occurs
On the 24 VDC supply
Integrated fuse
On the GND connection
No protection available
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 794: X20PD0016 - Technical data