X20 system User's Manual 3.10
297
4.3.13.8 Register description
4.3.13.8.1 Function model 0 - Standard
Read
Write
Register
Name
Data type
Cyclic
Non-cyclic
Cyclic
Non-cyclic
Analog signal - Configuration
16
USINT
●
18
UINT
●
20
INT
●
22
INT
●
Analog signal - Communication
Index * 2 - 2 AnalogInput0N (Index N = 1 to 8)
INT
●
30
USINT
●
31
USINT
●
4.3.13.8.2 Function model 254 - Bus controller
Read
Write
Register
Offset
1)
Name
Data type
Cyclic
Non-cyclic
Cyclic
Non-cyclic
Analog signal - Configuration
16
-
USINT
●
18
-
UINT
●
20
-
INT
●
22
-
INT
●
Analog signal - Communication
Index * 2 - 2
Index * 2 - 2 AnalogInput0N (Index N = 1 to 8)
INT
●
30
-
USINT
●
31
-
USINT
●
1)
The offset specifies the position of the register within the CAN object.
4.3.13.8.3 Analog inputs
Input signals are converted asynchronously in a 1 ms interval.
4.3.13.8.4 Analog input values
Name:
AnalogInput01 to AnalogInput08
The analog input values are mapped to this register.
Data type
Value
Input signal:
INT
0 to 32767
Current signal 0 to 20 mA or 4 to 20 mA
4.3.13.8.5 Input filter
This module is equipped with a configurable input filter.
4.3.13.8.5.1 Input ramp limitation
Input ramp limitation can only take place when a filter is used; the input ramp is limited before filtering takes place.
The amount the input value changes is checked to make sure that specified limits are not exceeded. If the values
are exceeded, the adjusted input value is equal to the old value ± the limit value.
Configurable limit values:
Value
Limit value
0
The input value is used without limitation.
1
0x3FFF = 16383
2
0x1FFF = 8191
3
0x0FFF = 4095
4
0x07FF = 2047
5
0x03FF = 1023
6
0x01FF = 511
7
0x00FF = 255