X20 system modules • X20 interface module communication • X20IF10A1-1
1834
X20 system User's Manual 3.10
4.23.18.3 Technical data
Product ID
X20IF10A1-1
Short description
Communication module
AS interface master
General information
B&R ID code
0xA718
Status indicators
Module status, network status, data transfer
Diagnostics
Module status
Yes, using status LED and software
Network status
Yes, using status LED and software
Data transfer
Yes, using status LED
Fieldbus power consumption
Max. 27 mA
Power consumption
Bus
1.1 W
Fieldbus
0.85 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
PLC - IF1
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
IF1 interface
Fieldbus
AS interface master
Design
4-pin male multipoint connector
Power supply
ASi power supply
Voltage range
24 to 32 V
Controller
netX100
Max. number of slaves
62
Max. distance
Standard
100 m
With additional components
500 m
Max. cycle time
5 ms
Response time
Typical 3 ms
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x TB704 terminal block separately
Slot
In the X20 CPU and in the X20BC1083 expandable bus controller
Table 625: X20IF10A1-1 - Technical data
Summary of Contents for X20 System
Page 2: ......