X20 system modules • Analog input modules • X20AI2222
150
X20 system User's Manual 3.10
Example 2
A disturbance interferes with the input value. The diagram shows the calculated value with the following settings:
Input ramp limitation = 0
Filter level = 2 or 4
0
8000
16000
t [ms]
1
2
3
4
5
6
7
8
Input value
Calculated value: Filter level 2
Calculated value: Filter level 4
Disturbance (spike)
Figure 59: Calculated value during disturbance
4.3.3.8.6 Configuring the input filter
Name:
ConfigOutput01
This register is used to define the filter level and input ramp limitation of the input filter.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
000
Filter switched off
001
Filter level 2
010
Filter level 4
011
Filter level 8
100
Filter level 16
101
Filter level 32
110
Filter level 64
0 - 2
Defines the filter level
111
Filter level 128
3
Reserved
0
000
The input value is used without limitation
001
Limit value = 0x3FFF (16383)
010
Limit value = 0x1FFF (8191)
011
Limit value = 0x0FFF (4095)
100
Limit value = 0x07FF (2047)
101
Limit value = 0x03FF (1023)
110
Limit value = 0x01FF (511)
4 - 6
Defines the input ramp limitation
111
Limit value = 0x00FF (255)
7
Reserved
0
4.3.3.8.7 Lower limit value
Name:
ConfigOutput03
This register can be used to configure the lower limit for analog values. If the analog value goes below the limit
value, it is frozen at this value and the corresponding error status bit is set.
Data type
Value
INT
-32,768 to 32,767
Information:
The default value of -32768 corresponds to the minimum default value of -10 VDC.
Keep in mind that this setting applies to all channels!