X20 system modules • X20 CPUs • X20CP158x and X20CP358x
920
X20 system User's Manual 3.10
Product ID
X20CP3583
X20CP3584
X20CP3585
X20CP3586
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
See section "Derating"
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order application memory
(CompactFlash) separately
Backup battery in-
cluded in delivery
X20 locking plate (right)
included in delivery
X20 terminal block (12-
pin) included in delivery
Interface module slot cov-
ers included in delivery
Order application memory (CompactFlash) separately
Backup battery included in delivery
X20 locking plate (right) included in delivery
X20 terminal block (12-pin) included in delivery
Interface module slot covers included in delivery
Dimensions
Width
200 mm
Height
99 mm
Depth
85 mm
Weight
470 g
Table 280: X20CP3583, X20CP3584, X20CP3585, X20CP3586 - Technical data
1)
The specified values are maximum values. The exact calculation is included as a data sheet in the module documentation and can be downloaded from
the B&R website.
2)
When operated at temperatures above 55°C, a derating of the rated output current to 5 W for the X2X Link supply must be taken into consideration.
3)
In parallel operation, only 75% of the rated power can be assumed. It is important to make sure that all power supplies operating in parallel are switched
on and off at the same time.
4)
Can be configured in Automation Studio.
5)
1 MB SRAM minus the configured remanent variables.
6)
See the POWERLINK help system under "General information, Hardware - IF/LS".