X20 system modules • Motor controllers • X20MM3332
1932
X20 system User's Manual 3.10
4.25.3.4 LED status indicators
For a description of the various operating modes, see the 2.11.1 "re LEDs" section.
Figure
LED
Color
Color
Description
Off
No power to module
Single flash
RESET mode
Blinking
PREOPERATIONAL mode
r
Green
On
RUN mode
Off
No power to module or everything OK
e
Red
On
Error or reset status
e + r
Red on / Green single flash
Invalid firmware
On
The corresponding output is active
Blinking
Error on the corresponding output
1 - 3
Orange
Off
The corresponding output is switched off
4.25.3.5 Pinout
Lines with a cross section between a minimum of 0.75 mm² and a maximum of 2.5 mm² are recommended for
the outputs.
Warning!
The terminal block is not permitted to be plugged in or unplugged during operation.
1
X
20
M
M
3
33
2
2
Motor 1 +
Motor 2 +
Motor 3 +
Motor 1 -
Motor 2 -
Motor 3 -
GND
GND
+24 VDC
+24 VDC
33
r
e
4.25.3.6 Connection example
_
+
GND
+24 VDC
GND
+24 VDC
MM
Motor
24 VDC
M
Inductance
Actuator