X20 system modules • Digital output modules • X20DO8332
X20 system User's Manual 3.10
1275
Environmental temperature: 60°C, 4 outputs (1,3,5,7 or 2,4,6,8) with the same load.
Switching voltage:
28.8 V
24.0 V
Coil resistance
[Ω]
Coil inductance
Max. switching cycles / second
(with 90% duty cycle)
0.1
1
10
100
10 mH
100 mH
1 H
10 H
100 H
100
500
10
Figure 396: Switching inductive loads
Environmental temperature: 60°C, all outputs with the same load.
28.8 V
24.0 V
0.1
1
10
100
Coil resistance
[Ω]
Coil inductance
10 mH
100 mH
1 H
10 H
100 H
100
500
10
Switching voltage:
Max. switching cycles / second
(with 90% duty cycle)
Figure 397: Switching inductive loads
Information:
If the maximum number of operating cycles per second is exceeded, an external inverse diode must
be used.
Operating conditions outside of the area in the diagram are not permitted!