X20 system modules • X20 electronics module communication • X20CS1011
X20 system User's Manual 3.10
1463
Product ID
X20CS1011
Environmental conditions
Temperature
Operation
Horizontal installation
0 to 55°C
Vertical installation
0 to 50°C
Derating
-
Storage
-25 to 70°C
Transport
-25 to 70°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order SmartWire attachment cable X20CA4S00.00xx separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 452: X20CS1011 - Technical data
1)
Using an external feed makes it possible to shut down via E-stop or switching relay
4.18.2.4 LED status indicators
For a description of the various operating modes, see the 2.11.1 "re LEDs" section.
Figure
LED
Color
Status
Description
Off
No power to module
Single flash
RESET mode
Blinking
PREOPERATIONAL mode
r
Green
On
RUN mode
Off
No power to module or everything OK
On
Error or reset status
e
Red
Single flash
Warning/Error on an I/O channel
e + r
Red on / Green single flash
Invalid firmware
S + R
Green
The "S" and "R" LEDs indicate the status of the SmartWire interface.
Off
U-Aux supply missing or too low
A
Green
On
U-Aux supply OK
"S" and "R" LEDs
The status of the SmartWire interface is indicated by the "S" and "R" LEDs.
S
R
Firmware status
Description
CHECK_INT_FRAM
Initialization
CHECK_LIN_SUPPLY
Wait until 17 VDC bus is OK
Off
Off
INT_ERROR_STATE
Internal error has occurred (remains)
SET_TRANSCEIVER_MODE Initialization of transceiver
RESET_UART
Initialization of UART + 10 ms delay
Off
On
READ_REVISION_CNT
Initialization (revision counter from FLASH)
INIT_LIN_SCAN
Initialization for bus scan
RUN_LIN_SCAN
Perform bus scan
INIT_LIN_SETUP
Initialization for RUN_LIN_SETUP
RUN_LIN_SETUP
Perform bus setup
STORE_REVISION_CNT
Revision counter in FLASH
Blinking slowly
Blinking slowly
WAIT_FOR_PUSHBUTTON
Wait for configuration button after bus scan and difference with existing config-
uration
Blinking slowly
Blinking quickly
TIME_DELAY
4 s optical confirmation signal after pressing the configuration button
DP_CFG_CHECK
Check of the configuration by the higher-level CPU (not currently used)
SET_SLAVES_TO_OP
Switch SmartWire stack to Operational
SET_SLAVES_TO_PREOP
Switch SmartWire stack to Preoperational
INIT_LIN_SCHED
Initialization for RUN_LIN_SCHED
On
Blinking slowly
RUN_LIN_SCHED (PREOP)
RUN SmartWire scheduler (in PREOP)
On
On
RUN_LIN_SCHED (OP)
RUN SmartWire scheduler (in OP)
Blinking slowly
On
IDLE_STATE
RUN SmartWire without scheduler (no slaves connected)
Blinking quickly
On
LIN_ERROR_STATE
ERROR LIN-BUS has occurred (remains)
Summary of Contents for X20 System