X20 system modules • Counter modules • X20DC4395
852
X20 system User's Manual 3.10
Product ID
X20DC4395
Measurement type
Continuous or triggered
Digital outputs
Design
Push / Pull / Push-Pull
Quantity
4
Nominal voltage
24 VDC
Switching voltage
24 VDC -15% / +20%
Nominal output current
0.1 A
Total nominal current
0.4 A
Output circuit
Sink or source
Output protection
Thermal cutoff if overcurrent or short circuit occurs, integrated protection for switching inductances
Pulse width modulation
1)
Period duration
41.6 µs to 1.36 s
Factor for period duration
n/48000 s, n = 2 to 65535
Pulse duration
0 to 100%
Resolution for pulse duration
0.1%
Actuator supply
Module-internal, max. 600 mA
Diagnostic status
Output monitoring
Leakage current when switched off
Max. 25 µA
Residual voltage
<0.9 V at 0.1 A rated current
Peak short circuit current
<10 A
Switching on after overload or short circuit cutoff
Approx. 10 ms (depends on the module temperature)
Switching delay
0 -> 1
<2 µs
1 -> 0
<2 µs
Switching frequency
Resistive load
Max. 24 kHz
Inductive load
See section "Switching inductive loads"
Braking voltage when switching off inductive loads
Switching v 0.6 VDC
Isolation voltage between channel and bus
500 V
eff
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 256: X20DC4395 - Technical data
1)
Dead time when switching between push and pull: max. 1.5 µs.