Coated modules • X20 interface module communication • X20cIF2181-2
2626
X20 system User's Manual 3.10
5.20.9.3 Technical data
Product ID
X20cIF2181-2
Brief description
Communication module
1x POWERLINK managing or controlled node
General information
B&R ID code
0xE23A
Status indicators
Module status, bus function
Diagnostics
Module status
Yes, using status LED and software
Bus function
Yes, using status LED and software
POWERLINK cable redundancy system
Configurable
Controller redundancy
Configurable
Power consumption
2.0 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
PLC - X1
Yes
PLC - X2
Yes
Certification
CE
Yes
GOST-R
Yes
Interfaces
Fieldbus
POWERLINK managing or controlled node
Type
Type 5
1)
Design
2x shielded RJ45 port
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
100 Mbit/s
Transmission
Physical interfaces
100 BASE-TX
Half-duplex
Yes
Full-duplex
No
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Controller
POWERLINK MAC
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Slot
In X20c CPU
Table 1013: X20cIF2181-2 - Technical data
1)
See the POWERLINK online help documentation under "General information - IF/LS hardware".
Summary of Contents for X20 System