X20 system modules • Digital output modules • X20DO4649
X20 system User's Manual 3.10
1191
Product ID
X20DO4649
Switching voltage
Max. 110 VDC / 250 VAC
Rated frequency
DC / 45 to 63 Hz
Nominal output current
5.0 A at 30 VDC / 5.0 A at 240 VAC
Total nominal current
10.0 A at 30 VDC / 10.0 A at 240 VAC
Actuator supply
External
Contact resistance
15 mΩ at 6 VDC / 1A
Switching delay
0 -> 1
≤10 ms
1 -> 0
≤10 ms
Isolation voltage
Contact - Contact
Tested at 750 VAC
Contact - Coil
Tested at 2300 VAC
Service life
Electrical
2)
Min. 5 x 10
4
ops. (NO) at 5 A
Mechanical
Min. 2 x 10
7
ops
Switching capacity
Minimum
0.05 W / 2.4 VA
Maximum
150 W / 1250 VA
Protective circuit
Internal
None
External
AC
RC combination or VDR
DC
Inverse diode, RC combination or VDR
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
When operated at temperatures above 55°C, the maximum current
per channel is reduced to 4 A and the maximum total current to 8 A.
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 378: X20DO4649 - Technical data
1)
Number of outputs x Contact resistance x Nominal output current
2
(A calculation example can be found on the B&R website in the download area for the
module.)
2)
With a resistive load. See also section "Electrical service life"