X20 system modules • Bus modules • X20BM05
586
X20 system User's Manual 3.10
4.7.3 X20BM05
4.7.3.1 General information
The X20BMx5 safety bus modules have node number switches that can be used to set permanent addresses.
Placing one of these modules at the beginning of an X20 block ensures a unique address. The addresses of
subsequent modules are automatically set in ascending order starting at this address. This simple feature greatly
increases the flexibility of applications.
Another advantage: Addresses can be set independently of which specific I/O modules are used. All that is required
are the respective bus modules. This provides logistical advantages with respect to cost and the variety of parts.
•
The X20BM05 is the base for all X20 supply modules
•
For creating voltage groups
•
The internal I/O supply is isolated to the left
•
Manual node number assignment
•
Independent of electronics module
•
Manual and automatic addressing can be combined as desired
4.7.3.2 Order data
Model number
Short description
Figure
Bus modules
X20BM05
X20 supply bus module with node number switch, internal I/O
supply is isolated to the left
Table 185: X20BM05 - Order data
4.7.3.3 Technical data
Product ID
X20BM05
Short description
Bus module
Supply bus module, internal I/O supply is isolated to the left, manual node number assignment
General information
Power consumption
Bus
0.13 W
Internal I/O
-
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
I/O supply
Nominal voltage
24 VDC
Permitted contact load
10.0 A
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0,5°C per 100 m
Protection in accordance with EN 60529
IP20
Table 186: X20BM05 - Technical data