4.26.4.9.4 Configuration registers
4.26.4.9.4.1 Excitation time
Name:
ConfigOutput02
The excitation time is configured in this register.
The output is switched fully on for the time set in this register after the module is switched on. After the excitation
time expires, the module goes into PWM mode.
Data type
Value
Information
USINT
0 to 255
In steps of 100 µs or 1000 µs
4.26.4.9.4.2 PWM ratio
Name:
ConfigOutput03
The PWM ratio between switch-off time and period duration is set in this register (in percent).
Data type
Value
Information
0
Permanently switched off
1 to 99
Ratio = switch-off time / period duration (1 to 99%)
USINT
100
Permanently switched off
4.26.4.9.4.3 Module configuration
Name:
ConfigOutput04
This register is used to configure the module's general parameters.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
0
1 kHz
0
PWM frequency
1
50 kHz
1
Reserved
0
100 µs
2
Excitation time base
1
1000 µs
3
Reserved
0
Low-point method
4
Switching point search
1
Curvature method
5 - 7
Reserved
4.26.4.9.4.4 Current and time differential
Name:
ConfigOutput05 to ConfigOutput20
The switching point search is configured with the parameters dI and dt in these non-cyclic registers.
•
dI - Current differential in LSB
•
dt - Time differential in 100 μs steps
For a sample configuration, see 4.26.4.9.6 "Configuring dI and dt"
Data type
Value
USINT
0 to 255
Registers
Description
ConfigOutput05
d
I
ConfigOutput06
d
t
Channel 1
...
...
ConfigOutput19
d
I
ConfigOutput20
d
t
Channel 8