X20 system modules • X20 interface module communication • X20IF2772
X20 system User's Manual 3.10
1875
4.23.26.3 Technical data
Product ID
X20IF2772
Short description
Communication module
2x CAN bus
General information
B&R ID code
0x1F25
Status indicators
Module status, data transfer, terminating resistor
Diagnostics
Module status
Yes, using status LED
Data transfer
Yes, using status LED
Terminating resistor
Yes, using status LED
Power consumption
1.2 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
IF1 - IF2
Yes
PLC - IF1
Yes
PLC - IF2
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
Interfaces
IF1 interface
Signal
CAN bus
1)
Design
5-pin male multipoint connector
Max. distance
1000 m
Transfer rate
Max. 1 Mbit/s
Terminating resistors
Integrated in the module
Controller
SJA 1000
IF2 interface
Signal
CAN bus
1)
Design
5-pin male multipoint connector
Max. distance
1000 m
Transfer rate
Max. 1 Mbit/s
Terminating resistors
Integrated in the module
Controller
SJA 1000
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 2x TB2105 terminal blocks separately
Slot
In X20 CPU
Table 656: X20IF2772 - Technical data
1)
This CAN bus interface can be configured as a CANopen master in Automation Studio 3.0 and higher.
Summary of Contents for X20 System
Page 2: ......