X20 system modules • Digital output modules • X20DO6325
X20 system User's Manual 3.10
1213
4.15.19.6 Connection example
GND
+24 VDC
GND
+24 VDC
DO
Actuator 5
Actuator 3
Actuator 1
Actuator 6
Actuator 4
Actuator 2
Figure 362: Connection example
Caution!
If the module is operated outside of specifications, the output current can increase above the maximum
permissible nominal current. This applies to individual channels and also to the summation current
for the module.
Therefore sufficient cable cross sections or external safety measures must be used.
4.15.19.7 OSP hardware requirements
In order to best use OSP mode, make sure when creating the application that the output module and CPU have
separate power supplies.
4.15.19.8 Output circuit diagram
Logic
High-side
24 V
GND
GND
Output x
I/O status
LED (orange)
Output
monitoring
Output status
200 kOhm for open line monitoring
Figure 363: Output circuit diagram