X20 system modules • Temperature modules • X20AT4222
X20 system User's Manual 3.10
2407
4.31.4.8.8 Input filter
Name:
ConfigOutput01
This register can be used to configure the filter time for all analog inputs.
Data type
Value
Filters
Filter time
0
15 Hz
66.7 ms
1
25 Hz
40 ms
2
30 Hz
33.3 ms
3
50 Hz
20 ms
4
60 Hz
16.7 ms
5
100 Hz
10 ms
6
500 Hz
2 ms
USINT
7
1000 Hz
1 ms
4.31.4.8.9 Sensor configuration
Name:
ConfigOutput02
This register can be used to configure the sensor type for individual channels.
This module is designed for temperature and resistance measurement. The sensor type must be specified because
of the different calibration values for temperature and resistance.
The default setting for all channels is ON. To save time, individual channels can be switched off (see "Reduced
Data type
Value
UINT
See bit structure.
Bit structure:
Bit
Name
Value
Information
0000 - 0001 Reserved
0010
Sensor type PT100
0011
Sensor type PT1000
0100
Reserved
0101
Resistance measurement 0.1 Ω to 4500 Ω
0110
Resistance measurement 0.05 Ω to 2250 Ω
0 - 3
Channel 1
1111
Channel disabled
...
...
0000 - 0001 Reserved
0010
Sensor type PT100
0011
Sensor type PT1000
0100
Reserved
0101
Resistance measurement 0.1 Ω to 4500 Ω
0110
Resistance measurement 0.05 Ω to 2250 Ω
12 - 15
Channel 4
1111
Channel disabled