4.8.4.3 Technical data
Product ID
X20BT9400
Short description
Bus transmitter
X2X Link bus transmitter with supply for I/O and integrated supply for the X67 system
General information
B&R ID code
0xA238
Status indicators
X2X bus function, operating status, module status
Diagnostics
Module run/error
Yes, using status LED and software
X2X bus function
Yes, using status LED
Power consumption
1)
Bus
0.5 W
Internal X67 X2X Link
1.38 W
Internal I/O
As bus transmitter
0.1 W
Additionally as supply module
0.6 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
X67 X2X Link supply input
Input voltage
24 VDC -15% / +20%
Input current
Max. 0.5 A
Fuse
Integrated, cannot be replaced
Reverse polarity protection
Yes
X67 X2X Link supply output
Parallel connection with X67PS1300
Yes
2)
Overload behavior
Temporarily protected against short circuit, overload
Be aware of corresponding status message (LED "I") or evaluate software status
X67 modules supplied by BT9400
Horizontal installation
Max. 8 (Nominal output power: 6 W)
Vertical installation
Max. 6 (Nominal output power: 4.5 W)
Input I/O supply
Input voltage
24 VDC -15% / +20%
Fuse
Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection
No
Output I/O supply
Rated output voltage
24 VDC
Behavior if a short circuit occurs
Required line fuse
Permitted contact load
10 A
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 or 1x X20BM15 bus module separately
Spacing
12.5
+0.2
mm
Table 206: X20BT9400 - Technical data