X20 system modules • Digital signal processing modules • X20DS1828
1338
X20 system User's Manual 3.10
Product ID
X20DS1828
Power consumption
Bus
0.01 W
Internal I/O
1.3 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Channel - Bus
Yes
Channel - Channel
No
Type of signal lines
Shielded cables should be used for all signal lines
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Encoder inputs
Angular position resolution
13-bit, with a 1 V
SS
signal
Encoder monitoring
Yes
Max. encoder cable length
10 m
Sine/Cosine inputs
Signal transmission
Differential signals, symmetric
Signal frequency
DC up to 200 kHz
Differential voltage
1 V
SS
Common-mode voltage
Max. ±10 V
Terminating resistor
120 Ω
Encoder supply
Output voltage
11 V
Load capability
150 mA
Protective measures
Overload protection
Yes
Short circuit protection
Yes
Parameter channel (RS485)
Signal transmission
5 VDC differential signal, EiA RS-485 standard
Transmission status
See HIPERFACE specification
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Protection in accordance with EN 60529
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
When operated at temperatures above 55°C, the power consumption of
the modules to the left and right of this module must not exceed 1.15 W.
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 428: X20DS1828 - Technical data