X20 system modules • Counter modules • X20DC1196
684
X20 system User's Manual 3.10
4.11.5 X20DC1196
4.11.5.1 General information
The module is equipped with 1 input for an ABR incremental encoder with 5 V encoder signal.
•
1 ABR incremental encoder 5 V
•
2 additional inputs e.g. for home enable switch
•
5 VDC, 24 VDC and GND for encoder supply
4.11.5.2 Order data
Model number
Short description
Figure
Counter functions
X20DC1196
X20 digital counter module, 1 ABR incremental encoders, 5 V,
600 kHz input frequency, 4x evaluation
Required accessories
Bus modules
X20BM11
Bus module, 24 VDC keyed, internal I/O supply continuous
Terminal blocks
X20TB12
X20 terminal block, 12-pin, 24 VDC keyed
Table 229: X20DC1196 - Order data
4.11.5.3 Technical data
Product ID
X20DC1196
Brief description
I/O module
1 ABR incremental encoder 5 V
General information
B&R ID code
0x1BAF
Status indicators
I/O function per channel, operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Power consumption
Bus
0.01 W
Internal I/O
1.5 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Encoder - Bus
Yes
Channel - Bus
Yes
Channel - Encoder
No
Channel - Channel
No
Type of signal lines
Shielded cables must be used for all signal lines.
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
Digital inputs
Quantity
2
Nominal voltage
24 VDC
Input voltage
24 VDC -15% / +20%
Input current at 24 VDC
Approx. 3.3 mA
Input filter
Hardware
≤2 μs
Software
-
Connection type
3-wire connections
Input circuit
Sink
Additional functions
Home enable switch
Table 230: X20DC1196 - Technical data
Summary of Contents for X20 System