4.26.5.9.9.4 CycleTime
Name:
CycleTime01 to CycleTime04
Some IO-Link devices cannot handle high-speed cycles and require a higher cycle time. This register can be used
to read back the channel's IO-Link cycle time currently being used. The time used for communication is always a
multiple of 100 µs, e.g. 50 for 5 ms cycle time.
Data type
Value
Information
UINT
0 to 65535
Specified in 100 μs steps
4.26.5.9.9.5 CycleMultible
Name: CycleMultible01 to CycleMultible04
This register can be used to read back the multiplicator currently being used for the channel's IO-Link cycles.
Data type
Value
UINT
0 to 65,535
4.26.5.9.9.6 CycleDivisor
Name:
CycleDivisor01 to CycleDivisor04
This register can be used to read back the divisor currently being used for the channel's IO-Link cycles.
Data type
Value
UINT
0 to 65,535
4.26.5.9.9.7 MinCycleTime
Name:
MinCycleTime01 to MinCycleTime04
This register can be used to read back the minimum IO-Link cycle time. The minimum IO-Link cycle time depends
on the IO-Link device and is read from the module after establishing communication with the IO-Link device.
Data type
Value
UINT
0 to 65,535
4.26.5.9.9.8 PDI_Size
Name:
PDI_Size01 to PDI_Size04
This register can be used to read back the size of the input process data defined by the device. This value is read
when starting up the IO-Link device.
Data type
Value
USINT
0 to 255
4.26.5.9.9.9 PDO_Size
Name:
PDO_Size01 to PDO_Size04
This register can be used to read back the size of the output process data defined by the device. This value is
read when starting up the IO-Link device.
Data type
Value
USINT
0 to 255
4.26.5.9.9.10 Baud rate
Name:
Baudrate01 to Baudrate04
This register can be used to read back the baud rate defined by the IO-Link device. This value is read when starting
up the IO-Link device.
Data type
Value
Information
1
COM1 = 4.8 kbit/s
2
COM2 = 38.4 kbit/s
USINT
3
COM3 = 230.4 kbit/s