E6581611
B-6
2
2.3
Description of terminals
2.3.1
Power circuit terminals
■
Connections with peripheral equipment
Motor
Power
supply
Inverter
Braking resistor
Molded-case
circuit braker
R/L1
S/L2
T/L3
PA/+ PB
V/T2
U/T1
W/T3
M
Magnetic
contactor
Input AC
reactor
noise
reduction filter
Zero-phase
reactor
Note 1: The T/L3 terminal is not provided for any single-phase models. So if you are using single-phase
models, use the R/L1 and S/L2/N terminals to connect power cables.
■
Power circuit
Terminal symbol
Terminal function
Grounding terminal for connecting inverter. There are 3 terminals in cooling fin or
mounting part of EMC plate.
R/L1,S/L2,T/L3
240V class : Three-phase 200 to 240V-50/60Hz
: Single-phase 200 to 240V-50/60Hz
500V class : Three-phase 380 to 500V-50/60Hz
* Single-phase inputs are R/L1 and S/L2/N terminals.
U/T1,V/T2,W/T3
Connect to three-phase motor.
PA/+, PB
Connect to braking resistors.
Change parameters
,
,
,
if necessary.
PA/+
This is a positive potential terminal in the internal DC main circuit.
DC common power can be input with PC/- terminal.
PC/-
This is a negative potential terminal in the internal DC main circuit.
DC common power can be input with PA/+ terminal.
PO, PA/+
Terminals for connecting a DC reactor (DCL: optional external device). Shorted by a
short bar when shipped from the factory. Before installing DCL, remove the short bar.
The arrangements of power circuit terminals are different from each range.
Refer to section 1.3.3.1) for details.