14
Q9 Plus Bypass ASD/Bypass Box Installation and Operation Manual
The three positions of
SW2
(
Off
,
INV
, and
BYP
) are described below.
Off
—
K2
and
K3
remain in the normal state.
INV
— Energizes
K2
which turns off
LED 1
(Test Mode) (if on), illuminates
LED 2
(INV Mode),
opens
K2
at Stage 3, closes
K2
at Stage 4, and completes the
ST
terminal path via PCB 11. The
resulting closure of
K2
at Stage 4 energizes the
2M
contactor (jumper or open-damper signal at DRA/
B required), which allows the ASD output to be applied to the motor (see 2M at
).
BYP
— Energizes
K3
which turns off
LED 2
(INV Mode) (if on), illuminates
LED 3
(Bypass
Mode),
opens
K2
at Stage 4 (which opens 2M if closed), and closes
K3
at Stage 4. The resulting
closure of
K3
at Stage 4 energizes the
3M
contactor (jumper or open-damper signal at DRA/B
required), which allows the utility power to be applied directly to the motor bypassing the ASD (see
3M at
).
Note:
Ensure that the phase relationship of the
L1
,
L2
, and
L3
connections to the motor for
the
Bypass
mode of operation and for the ASD-driven operation are consistent. The
Reverse
and
Forward
functions will be reversed if not properly connected (see
).
The
Damper Response
feedback circuit (DRA/DRB) may be used to prevent a motor from attempting
to force air flow through a duct that has a closed damper.
Damper motor power (120 VAC) is provided from an external source and is applied via the switched
DSA/DSB
circuit (
contacts). The 120 VAC is switched via the
OUT1
contacts while operating in
the
INV
mode or switched via the
K3
contacts while operating in the
Bypass
mode.
Note:
OUT1
contacts are labeled
DSA
and
DSB
on the
.
Stage 4 Function
In the
INV
mode, the
OUT1
closure (set to Damper Command) occurs upon receiving a
Run
command
and allows power to be applied to the damper motor. Once the damper-mounted
DRA
-to-
DRB
contacts
are closed (open damper required),
K4
is energized.
LED 4
(System Interlock) illuminates and the
K4
contacts close the
S3
-to-
CC
connection (
JP1
jumper
required), completing the
Damper Feedback
circuit requirement for ASD operation. The
DRA
-to-
DRB
closure also provides power to the
2M
coil allowing for the ASD output to be applied to the motor
while operating in the
INV
mode.
If no discrete input terminal is assigned the function Damper Feedback, this permissive
will not be a requirement for normal system operation.
With all other permissives configured to run, the motor will run without activating a
Damper Feedback discrete input terminal.
In the
Bypass
mode,
K3
is energized via
SW2
. The
K3
contact closure at PCB 11 applies power to the
damper motor (
jumpers JPDS1 and JPDS2 are required). Once the damper-mounted
DRA
-to-
DRB
contacts are closed (open damper required), the
3M
coil is energized and provides utility
power to the motor, bypassing the ASD.
The
DRA
-to-
DRB
contacts are provided via a reversible damper-mounted switch. The switch
terminates power to the damper motor once the damper is fully opened or closed (reversible means that
only the opposite function is available once reaching the fully opened or closed position).