E6581611
F-89
6
Set
f400
to
2
to before the start of operation. Tuning is performed at the start of the motor.
,
Precautions on auto-tuning
(1) Conduct auto-tuning after the motor has been connected properly and operation completely
stopped.
If auto-tuning is conducted immediately after operation stops, the presence of a residual voltage
may result in abnormal tuning.
(2) Voltage is applied to the motor during tuning even though it barely rotates. During tuning, “
”
is displayed on the operation panel.
(3) Tuning is performed when the motor starts for the first time after
f400
is set to
2
.
Tuning is usually completed within three seconds. If it is aborted, the motor will trip with the
display of
etn1
and no constants will be set for that motor.
(4) If special motors cannot be auto-tuned, perform manual tuning follow Selection 2 described
below.
(5) Provide cranes and hoists with sufficient circuit protection such as mechanical braking. Insufficient
motor torque while tuning may cause machine stalling/falling.
(6) If auto-tuning is impossible or an "
etn1
" auto-tuning error is displayed, perform manual tuning
with Selection 2.
[Selection 2: Setting PM motor control and manual tuning]
If an "
etn1
" tuning error is displayed during auto-tuning or when PM motor control characteristics are to be
improved, set motor constants manually.
[Parameter setting]
Title Function
Adjustment
range
Default
setting
f402
Automatic torque boost value
0.1-30.0 (%)
f405
Motor rated capacity
0.01-22.00 (kW)
f415
Motor rated current
0.1-100.0 (A)
Depends on
the capacity
(Refer to
section 11.4)
f417
Motor rated speed
100-64000 (min
-1
) *1
f459
Load inertia moment ratio
0.1-100.0 (times)
1.0
f462
Speed reference filter coefficient
0-100
35
f912
Q axis inductance per phase
0.01-650.0 (mH)
10.00
f913
D axis inductance per phase
0.01-650.0 (mH)
10.00
thr
Motor electronic thermal
protection level 1
10-100 (%) / (A)
100
*1: Default setting values vary depending on the setup menu setting.
Setting procedure Adjust the following parameters:
f402
: Adjust the primary resistive component of the motor. Decreases in torque due to a possible voltage
drop during low-speed operation can be suppressed by setting a large value in this parameter. Be
careful as setting a value larger than necessary may lead to an increased current causing a trip at
low speeds. (Perform adjustments according to the actual operation.) If the test report exists, see
the stator resistance value per phase.
f402
=
3
X Rs X
f415
/ Vtype X 100 [%]
Rs is Stator resistance per phase [ohm]) Vtype is 200 or 400 [V] (depend on voltage class)