E6581611
G-9
7
(3) Holding the output of signals in ON status
,
If the conditions for activating the functions assigned to RY-RC terminal and OUT terminal agree with and
as a result the output of signals is put in ON status, the output of signals is held ON, even if the conditions
change. (Output terminal holding function)
Assign function 80 to 83 to an input terminal.
Once RY-RC terminal or OUT terminal is turned on when the assigned input terminal is ON, RY-RC terminal
or OUT terminal is held ON.
Function No.
Code
Function
Action
80 HDRY
Holding of RY-RC terminal
output
ON : Once turned on, RY-RC are held on.
OFF: The status of RY-RC changes in real
time according to conditions.
82 HDOUT
Holding of OUT-NO terminal
output
ON : Once turned on, OUT-NO are held on.
OFF: The status of OUT-NO changes in real
time according to conditions.
Each one of the following numbers (81, 83) is an inverse signal.
Usage example ···operational signal, brake signal
Low-speed detection signal outputs the signal when the output frequency exceeds the setting of
f100
.
This signal can be used as an operation signal by setting
f100
to 0.0Hz. (Default setting)
This signal can also be used as an electromagnetic brake excitation/release signal.
Setting example) When outputting the brake signal from RY-RC terminal
Title Function Adjustment
range
Example of setting
f100
Low-speed signal output frequency
0.0 -
fh
(Hz)
2.5
f130
Output terminal selection 1A (RY-RC)
0-255
4:
LOW (Low-speed
detection signal)
Output frequency
Time [s]
Low-speed detection signal :
RY-RC terminals
ON
OFF
Inversion of low-speed
detection signal
ON
OFF
[Hz]
0
Setting frequency