<Frequency setting mode selection>
[Parameter setting]
Title
Function
Adjustment range
Default setting
Frequency setting mode selection 1
0: Setting dial 1(save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2(press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14:
sro
0
[Programmed value]
:
Setting dial 1
Frequencies are set by rotating the setting dial on the inverter. Like the position
of notches in a volume knob, the frequency setting value at the position of the
notch is saved.
⇒
Refer to section 3.2.2
:
Terminal VIA
A frequency command is set by means of external analog signals.
(VIA terminal: 0 –10Vdc)
⇒
Refer to section 3.2.2 and 7.3
:
Terminal VIB
A frequency command is set by means of external analog signals.
(VIB terminal: 0 - +10Vdc or -10 - +10Vdc)
⇒
Refer to section 3.2.2 and 7.3
:
Setting dial 2
Frequencies are set by rotating the setting dial on the inverter. Press the center
of the setting dial to save the frequency setting value.
⇒
Refer to section 3.2.2
:
RS485
communication
Frequencies are set by RS485 communication from an external device.
⇒
Refer to section 6.33
:
UP/DOWN from
external logic input
Frequencies are set by up/down commands from a terminal.
⇒
Refer to section 6.6.3
:
CANopen
communication
Frequencies are set by CANopen communication from an external device.
⇒
Refer to “CANopen communication Instruction Manual E6581911”.
:
Communication
option
Frequencies are set by commands from a communication option.
⇒
Refer to each Instruction Manual of option.