E6581611
F-51
6
6.15 Jump frequency - avoiding resonant frequencies
f270
: Jump frequency 1
f271
: Jumping width 1
f272
: Jump frequency 2
f273
: Jumping width 2
f274
: Jump frequency 3
f275
: Jumping width 3
•
Function
Resonance due to the natural frequency of the mechanical system can be avoided by jumping the
resonant frequency during operation. During jumping, hysteresis characteristics with respect to the jump
frequency are given to the motor.
Jumping width 1 (
)
Jumping width 2 (
)
Jumping width 3 (
)
Jump frequency 3
(
)
Jump frequency 1 (
)
Jump frequency 2 (
)
Output command frequency
(Hz)
Frequency setting signal
0
[Parameter setting]
Title
Function
Adjustment range
Default setting
f270
Jump frequency 1
0.0-
fh
(Hz)
0.0
f271
Jumping width 1
0.0-30.0 (Hz)
0.0
f272
Jump frequency 2
0.0-
fh
(Hz)
0.0
f273
Jumping width 2
0.0-30.0 (Hz)
0.0
f274
Jump frequency 3
0.0-
fh
(Hz)
0.0
f275
Jumping width 3
0.0-30.0 (Hz)
0.0
Note 1: Do not set the jump parameters, if multiple jump frequency setting width overlap.
Note 2: During acceleration or deceleration, the jumping function doesn’t work for the operation frequency.