[Selection 2: Setting vector control and auto-tuning independently]
Set vector control, automatic torque boost, energy saving and auto-tuning individually.
After setting
pt
(V/F control mode selection), auto-tuning starts.
Set the auto-tuning parameter
f400
to
2
(Auto-tuning enabled)
[Parameter setting]
Title
Function
Adjustment range
Default setting
f400
Auto-tuning
0: Auto-tuning disabled
1: Initialization of
f402
(after execution : 0)
2: Auto-tuning executed
(after execution: 0)
3: -
4: Motor constant auto calculation
(after execution: 0)
5: 4+2 (after execution: 0)
0
Set
f400
to
2
before the start of operation. Auto-tuning is performed at the start of the motor and set
f402
,
f412
.
,
Precautions on auto-tuning
(1) Conduct auto-tuning after the motor has been connected properly and operation completely
stopped.
If auto-tuning is conducted immediately after operation stops, the presence of a residual voltage
may result in abnormal tuning.
(2) Voltage is applied to the motor during tuning even though it barely rotates. During tuning,
“
” is displayed on the operation panel.
(3) Tuning is performed when the motor starts for the first time after
f400
is set to
2
.
Tuning is usually completed within three seconds. If it is aborted, the motor will trip with the
display of
etn1
and no constants will be set for that motor.
(4) High-speed motors, high-slip motors or other special motors cannot be auto-tuned. For these
motors, perform manual tuning using Selection 3 described below.
(5) Provide cranes and hoists with sufficient circuit protection such as mechanical braking. Insufficient
motor torque while tuning may cause machine stalling/falling.
(6) If auto-tuning is impossible or an "
etn1
" auto-tuning error is displayed, perform manual tuning
with selection 4.
[Selection 3: Setting vector control and motor constant automatically]
After setting
vl
,
vlv
,
f405
,
f415
and
f417
, motor constants calculated automatically.
f402
,
f412
and
f416
are set automatically.
Set the motor constant parameter
f400
to
4
(auto calculation)
Set
f400
=
5
, when auto-tuning is executed after setting motor constants automatically.