6.1
Parameters useful for settings and adjustments
6.1.1 Searching for changes using the history function (
auh
)
auh
: History function
History function (
auh
):
Automatically searches for 5 latest parameters that are programmed with values different from the
default setting and displays them in the
auh
. Parameter setting can also be changed within this
group
auh
.
How to use the history function
Operation panel
action
LED display
Operation
0
0
Displays the output frequency (operation stopped).
(When standard monitor display selection
f710
=
0
[output frequency])
auh
The first basic parameter “
auh
” (history function) is displayed.
acc
The parameter that was set or changed last is displayed.
8
0
Press the center of the setting dial to display the set value.
5
0
Turn the setting dial to change the set value.
5
0
acc
Press the center of the setting dial to save the changed value. The
parameter name and the programmed value will flash on and off
alternately.
****
Turn the dial as described above to search for and display changed
parameters to check and change the settings.
head
(
end
)
head
: First historic record
end
: Last historic record
Parameter
display
auh
fr
f
0
0
Press the MODE key to return to the parameter setting mode
“
auh
.”
After that you can press the MODE key to return to the status
monitor mode or the standard monitor mode (display of output
frequency).
MODE
MODE
MODE
MODE