E6581611
K-27
11
PM
motor
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0900
Factory specific
coefficient 9A
- -
-
- *3
0901
Factory specific
coefficient 9B
- -
-
-
0902
Factory specific
coefficient 9C
- -
-
-
0909
Factory specific
coefficient 9D
- -
-
-
0910 Step-out
detection
current level
%
1/1 1-150
100 6.39
0911 Step-out
detection
time
s
0.01/0.01
0.00: No detection
0.01-2.55
0.00
0912
q-axis inductance
mH 0.01/0.01
0.01-650.0 10.00
6.25.2
6.39
0913
d-axis inductance
mH 0.01/0.01
0.01-650.0 10.00
0914
Factory specific
coefficient 9E
- -
-
- *
3
0915
Factory specific
coefficient 9L
- -
-
-
0916
Factory specific
coefficient 9F
- -
-
-
0917
Factory specific
coefficient 9G
- -
-
-
0918
Factory specific
coefficient 9H
- -
-
-
0919
Factory specific
coefficient 9I
- -
-
-
0920 Factory
specific
coefficient 9J
- -
-
-
0930 Factory
specific
coefficient 9K
- -
-
-
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Traverse
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0980
Traverse selection
- 1/1
0:
Disabled
1: Enabled
0
6.40
0981
Traverse
acceleration time
s 0.1/0.1
0.1-120.0
25.0
0982
Traverse
deceleration time
s 0.1/0.1
0.1-120.0
25.0
0983
Traverse step
% 0.1/0.1
0.0-25.0
10.0
0984
Traverse jump
step
% 0.1/0.1
0.0-50.0
10.0