5.10.2 Displaying the motor or the line speed
f702
: Frequency free unit display magnification
f703
: Frequency free unit coverage selection
f705
: Inclination characteristic of free unit display
f706
: Free unit display bias
Function
The frequency or any other item displayed on the monitor can be converted into the rotational speed of
the motor or load device. The unit of the amount of processing or that of feedback can be changed at PID
control.
The value obtained by multiplying the displayed frequency by the
f702
-set value will be displayed as
follows:
Value displayed = Monitor-displayed or parameter-set frequency
f702
1)
Displaying the motor speed
To switch the display mode from 60Hz (default setting) to 1800min
-1
(the rotating speed of the 4P motor)
=
×
.
=
=
.
Hz
2)
Displaying the speed of the loading unit
To switch the display mode from 60Hz (default setting) to 6m/min
-1
(the speed of the conveyer)
Note: This parameter displays the inverter output frequency as the value obtained by multiplying it by a
positive number. This does not mean that the actual motor speed or line speed are indicated
with accuracy.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f702
Frequency free unit display
magnification
0.00: Disabled (display of frequency)
0.01-200.0 (times)
0.00
f703
Frequency free unit coverage
selection
0: All frequencies display
1: PID frequencies display
0
f705
Inclination characteristic of free unit
display
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1
f706
Free unit display bias
0.00-
fh
(Hz)
0.00
=
.
=
.
×
.
=
.
Hz