6.32 Analog input terminal function selection
f214
: VIB input point 1 rate
f215
: VIB input point 2 rate
f663
: Analog input terminal function selection (VIB)
•
Function
Parameter is normally set from operation panel. However some parameters can be continuously
set from
external
analog input by using
this function. VIB terminal is used.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f214
VIB input point 1 rate
-250-+250 (%)
0
f215
VIB input point 2 rate
-250-+250 (%)
100
f663
Analog input terminal function
selection
(VIB)
0: Frequency command
1: Acceleration/deceleration time
2: Upper limit frequency
3, 4: -
5: Torque boost value
6: Stall prevention level
7: Motor electronic-thermal protection level
8 to 10: -
11: Base frequency
0
+
Analog input terminal function assigns VIB terminal. The range of analog input voltage is 0% to +100%.
From -100% to 0% cannot be used.
+
The parameter that is selected by
f663
can be adjusted range as following table.
Setting of
f663
Object parameter
VIB : 0% input
VIB : 100% input
0: Frequency
command
- -
-
1: Acceleration/
deceleration time
acc
,
dec
,
f500
,
f501
,
f510
,
f511
Parameter setting value x
f214
Parameter setting value x
f215
2: Upper limit
frequency
ul
Parameter setting value x
f214
Parameter setting value x
f215
5: Torque boost
value
vb
,
f172
Parameter setting value x
f214
Parameter setting value x
f215
6: Stall prevention
level
f185
,
f601
Parameter setting value x
f214
Parameter setting value x
f215
7: Motor electronic-
thermal protection
level
thr
,
f173
Parameter setting value x
f214
Parameter setting value x
f215
11: Base frequency
vlv
,
f171
Parameter setting value x
f214
Parameter setting value x
f215
Note: Adjustments are made by the inverter itself, so no changes are made to parameter settings