E6581611
K-11
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0: Carrier frequency without reduction
1: Carrier frequency with automatic
reduction
2: Carrier frequency without reduction
Support for 500V models
0316 PWM
carrier
frequency control
mode selection
- -
3: Carrier frequency with automatic
reduction
Support for 500V models
1
6.18
0317 Synchronized
deceleration time
(time elapsed
between start of
deceleration to stop)
s 0.1/0.01
0.0-3600
(360.0)
2.0 6.19.2
0318 Synchronized
acceleration time
(time elapsed
between start of
acceleration to
achievement of
specified speed)
s 0.1/0.01
0.0-3600
(360.0)
2.0
0319 Regenerative
over-excitation
upper limit
% 1/1
100-160
*1
6.19.5
0320 Droop
gain
% 0.1/0.1
0.0-100.0
0.0 6.20
0323 Droop
insensitive
torque band
% 1/1
0-100
10
0324 Droop
output
filter
- 0.1/0.1
0.1-200.0
100.0
0325 Brake
releasing
waiting time
s 0.01/0.01
0.00-2.50
0.00 6.22.1
0326 Brake
releasing
small current
detection level
% 1/1
0-100
0
0327 Factory
specific
coefficient 3C
- -
-
- *
3
0328 Light-load
high-
speed operation
selection
- -
0:Disabled
1:High-speed operation speed set
automatically (Power running at F
command: Increase)
2:High-speed operation speed set
automatically (Power running at R
command: Increase)
3:High-speed operation speed set
with
f330
(Power running at F
command: Increase)
4:High-speed operation speed set
with
f330
(Power running at R
command: Increase)
0
6.21
0329 Light-load
high-
speed learning
function
- -
0:No
learning
1:Forward run learning
2:Reverse run learning
0
0330 Automatic
light-load
high-speed
operation frequency
Hz 0.1/0.01
30.0-
ul
*1
0331 Light-load
high-
speed operation
switching lower
limit frequency
Hz 0.1/0.01
5.0-
ul
40.0
0332 Light-load
high-
speed operation
load waiting time
s 0.1/0.1
0.0-10.0
0.5
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.