E6581611
F-49
6
6.14 Jog run mode
f260
: Jog run frequency
f261
: Jog run stopping pattern
f262
: Panel jog run mode
•
Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal immediately
generates a jog run frequency output irrespective of the designated acceleration time.
Also, you can choose the jog run start/stop mode from the panel.
Assign 18: jog run mode to an input terminal.
Ex) When assigning it to the RES terminal:
f113
to
18
.
The motor can be operated in jog mode while the assigned input terminals are connected (RES-CC ON).
[Parameter setting]
Title
Function
Adjustment range
Default setting
f260
Jog run frequency
f240
-20.0 (Hz)
5.0
f261
Jog run stopping
pattern
0: Deceleration stop
1: Coast stop
2: DC braking
0
f262
Panel jug run mode
0: Invalid
1: Valid
0
[Setting of jog run mode (RES-CC)]
Ex) Assign jog run mode to control terminal RES.
Title Function
Adjustment
range
Setting
f113
Input terminal selection (RES)
0-203
18
(Jog run mode)
Note 1: During the jog run mode, low speed detection signal (LOW) is output but designated frequency reach
signal (RCH) is not output, and PID control does not work.
Note 2: When only the operation panel is used for operation in jog run mode, the jog run function does not need to
be assigned to any input terminal.
<Examples of jog run>
RES (JOG): ON + F:ON: Forward jog run
RES(JOG): ON + R: ON: Reverse jog run
( Frequency c F: ON: Forward run , Frequency c R: ON: Reverse run )
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......