E6581611
E-1
5
5. Main
parameters
Here are described main parameters you set before use according to the section 11. Tables of parameters and data.
5.1
Meter setting and adjustment
: Meter selection
: Meter adjustment gain
Function
Output of 0 - 1mAdc, 0 (4) - 20mAdc, 0 - 10vdc can be selected for the output signal from the FM
terminal, depending on the
setting. Adjust the scale at
.
Use an ammeter with a full-scale 0 - 1mAdc meter.
The
(analog output bias) needs to be adjusted if output is 4 - 20mAdc.
[Parameter setting]
Title Function
Adjustment
range
Supposition output at
f
sl
=
17
Default setting
Meter
selection
0: Output frequency
1: Output current
2: Frequency command value
3: Input voltage (DC detection)
4: Output voltage (command value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor) cumulative
load factor
12:Stator frequency
13:VIA input value
14:VIB input value
15:Fixed output 1
(output current 100% equivalent)
16:Fixed output 2
(output current 50% equivalent)
17:Fixed output 3
(Other than the output current)
18:RS485 communication data
19:For adjustments (
set value is
displayed.)
20: VIC input value
21: Pulse train input value
22: -
23: PID feedback value
24: Integral input power
25: Integral output power
Maximum frequency (
)
-
Maximum frequency (
fh
)
1.5x rated voltage
1.5x rated voltage
1.85x rated power
1.85x rated power
2.5x rated torque
-
Rated load factor
Rated load factor
Rated load factor
Maximum frequency (
fh
)
Maximum input value
Maximum input value
-
-
-
Maximum value (100.0%)
-
Maximum input value
Maximum input value
-
Maximum frequency (
fh
)
1000x
f749
1000x
f749
0
Meter
adjustment
gain
- -
-
Resolution: All FM terminals have a maximum of 1/1000.