E6581611
E-14
5
5) Overload characteristic selection
aul
Overload characteristic of inverter can be selected to 150%-60s or 120%-60s.
[Parameters settings]
Title
Function
Adjustment range
Default setting
aul
Overload characteristic selection
0: -
1: Constant torque
characteristic
(
150%-60s
)
2: Variable torque
characteristic
(
120%-60s
)
0
,
Regarding to characteristic for
aul
=
1
setting, refer to section 3.5.3).
Note 1) In case of
aul
=
2
setting, be sure to install the input AC reactor (ACL) between power supply and inverter.
■
aul
=
2
(Variable torque characteristic),
f631
=
0
(120%-60s)
Inverter overload protection characteristic
60
100%: Inverter rated output current
time
[s]
Inverter overload
Monitored output current [%]
0
105%
120%
Current
[%]
Inverter overload time [s]
(Outline data)
106 900
110 180
115 90
120 60
140 2
165 0.5