E6581611
K-28
11
Factory
specific
parameters
Title Function
Reference
Factory specific coefficient
*3
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Communication option parameters
Title Function
Reference
,
Communication option common parameters
E6581913
CC-Link option parameters
E6581830
ProfiBus DP option parameters
E6581738
DeviceNet option parameters
E6581737
,
EtherCAT option parameters
E6581818
EtherNet common parameters
E6581741
EtherNet/IP option parameters
Modbus TCP option parameters
,
CANopen communication parameters
E6581911
Note) Refer to each Instruction Manual for option about detailed specifications.
11.4 Default settings by inverter rating
Torque
boost value
Dynamic
braking
resistance
Dynamic
braking
resistor
capacity
Automatic
torque
boost value
Motor rated
capacity
Motor rated
current
Motor
no-load
current
Over-
voltage stall
protection
level
Integrating
wattmeter
display unit
selection
Inverter type
/
(%)
(
Ω
)
(kW)
(%)
(kW)
(A)
(%)
(%)
VFS15-2004PM-W
6.0 200.0
0.12 6.2 0.40 2.0 65 136 0
VFS15-2007PM-W
6.0 200.0
0.12 5.8 0.75 3.4 60 136 0
VFS15-2015PM-W
6.0 75.0 0.12 4.3 1.50 6.2 55 136 0
VFS15-2022PM-W
5.0 75.0 0.12 4.1 2.20 8.9 52 136 0
VFS15-2037PM-W
5.0 40.0 0.12 3.4 4.00 14.8 48 136 1
VFS15-2055PM-W
4.0 15.0 0.44 3.0 5.50 21.0 46 136 1
VFS15-2075PM-W
3.0 15.0 0.44 2.5 7.50 28.2 43 136 1
VFS15-2110PM-W
2.0 7.5 0.88 2.3 11.00
40.6 41 136 1
VFS15-2150PM-W
2.0 7.5 0.88 2.0 15.00
54.6 38 136 1
VFS15S-2002PL-W
6.0 200.0
0.12 8.3 0.20 1.2 70 136 0
VFS15S-2004PL-W
6.0 200.0
0.12 6.2 0.40 2.0 65 136 0
VFS15S-2007PL-W
6.0 200.0
0.12 5.8 0.75 3.4 60 136 0
VFS15S-2015PL-W
6.0 75.0 0.12 4.3 1.50 6.2 55 136 0
VFS15S-2022PL-W
5.0 75.0 0.12 4.1 2.20 8.9 52 136 0
VFS15-4004PL-W 6.0 200.0
0.12 6.2 0.40 1.0 65 141 0
VFS15-4007PL-W 6.0 200.0
0.12 5.8 0.75 1.7 60 141 0
VFS15-4015PL-W 6.0 200.0
0.12 4.3 1.50 3.1 55 141 0
VFS15-4022PL-W 5.0 200.0
0.12 4.1 2.20 4.5 52 141 0
VFS15-4037PL-W 5.0 160.0
0.12 3.4 4.00 7.4 48 141 1
VFS15-4055PL-W 4.0 60.0 0.44 2.6 5.50 10.5 46 141 1
VFS15-4075PL-W 3.0 60.0 0.44 2.3 7.50 14.1 43 141 1
VFS15-4110PL-W 2.0 30.0 0.88 2.2 11.00 20.3 41 141 1
VFS15-4150PL-W 2.0 30.0 0.88 1.9 15.00 27.3 38 141 1
*1: When region setting is JP,
is set to 3.7(kW).
Summary of Contents for Q9 Plus ASD
Page 5: ...TM Q9 Plus Bypass ASD Bypass Box INSTALLATION OPERATION MANUAL June 2013 DN 68251 000 ...
Page 61: ...Q9 PLUS ASD LOW VOLTAGE DRIVE ...
Page 65: ...S15 ASD LOW VOLTAGE DRIVE ...
Page 80: ...E6581611 iv 15 Warranty O 1 16 Disposal of the inverter P 1 ...
Page 429: ......
Page 430: ......