E6581611
K-10
11
Operation
mode
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0300 PWM
carrier
frequency
kHz
0.1/0.1
2.0
-16.0
12.0 6.18
0301 Auto-restart
control selection
- -
0:
Disabled
1: At auto-restart after momentary
stop
2: At ST terminal off and on
3: 1+2
4: At start-up
0 5.9
0302 Regenerative
power ride-
through control
(Deceleration
stop)
- -
0:
Disabled
1: Regenerative power ride-through
control
2: Deceleration stop during power
failure
3: Synchronized acceleration /
deceleration (signal)
4: Synchronized acceleration /
deceleration ( power failure)
0
6.19.2
0303 Retry
selection
(number of times)
Times
1/1 0:
Disabled
1-10
0
6.19.3
0304 Dynamic
braking
selection
- -
0:
Disabled
1: Enabled, Resistor overload
protection enabled
2: Enabled
3: Enabled, Resistor overload
protection enabled
(At ST terminal on)
4: Enabled (At ST terminal on)
0
6.19.4
0305 Overvoltage
limit
operation
(Deceleration stop
mode selection)
- -
0:
Enabled
1: Disabled
2: Enabled (Quick deceleration
control)
3: Enabled (Dynamic quick
deceleration control)
2
6.19.5
0: Supply voltage uncorrected,
output voltage limited
1: Supply voltage corrected,
output voltage limited
2: Supply voltage uncorrected,
output voltage unlimited
0307 Supply
voltage
correction
(output voltage
limitation)
- -
3: Supply voltage corrected,
output voltage unlimited
*1
6.19.6
0308 Dynamic
braking
resistance
Ω
0.1/0.1
1.0-1000
*2 6.19.4
0309 Dynamic
braking
resistor capacity
kW 0.01/0.01
0.01-30.00
*2
0310 Factory
specific
coefficient 3A
- -
-
- *
3
0311 Reverse-run
prohibition
-
-
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0
6.19.7
0312 Random
mode -
- 0:
Disabled
1: Random mode 1
2: Random mode 2
3: Random mode 3
0
6.18
0314 Factory
specific
coefficient 3B
- -
-
- *
3
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.