6.29.8 Detection of output short-circuit
f613
: Detection of output short-circuit at start-up
•
Function
This parameter detects inverter output short-circuit. It can be usually detected in the length of the
standard pulse. When operating low-impedance motor such as high-speed motor, however, select the
short-time pulse.
f613
=
0
: Detection is executed in the length of the standard pulse every time you start up the inverter.
f613
=
1
: Detection is executed in the length of standard pulse only during the first start-up after putting on
the power or after resetting.
f613
=
2
: Detection is executed with the short-time pulse every time you start up the inverter.
f613
=
3
: Detection is executed with the short-time pulse only for the first time after putting power on or
after resetting.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f613
Detection of output short-circuit at
start-up
0: Each time (standard pulse)
1: Only one time after power on
(standard pulse)
2: Each time (short pulse)
3: Only one time after power on
(short pulse)
0
6.29.9 Ground fault detection function
f614
: Ground fault detection selection
•
Function
This parameter detects inverter ground fault. If a ground fault occurs in the inverter unit or output side,
the inverter will trip and the failure signal FL will be activated.
ef2
is displayed in the event of a trip.
f614
=
0
: No tripping. (Failure signal FL not activated)
f614
=
1
: Ground fault detection is enabled. The inverter will trip if the ground fault is occurred.
(Failure signal FL activated)
[Parameter setting]
Title
Function
Adjustment range
Default setting
f614
Ground fault detection selection
0: Disabled
1: Enabled
1
Note: When ground fault detection function sets to “Disabled”, installing of ground detector such as ground
relay is recommended.