E6581611
F-33
6
6.8
Basic parameters 2
6.8.1
Switching motor characteristics via terminal input
f170
: Base frequency 2
f171
: Base frequency voltage 2
f172
: Torque boost value 2
f173
: Motor electronic-thermal protection level 2
f185
: Stall prevention level 2
Function
Use the above parameters to switch the operation of two motors with a single inverter and to select
motor V/F characteristics (two types) according to the particular needs or operation mode.
Note: The
pt
(V/F control mode selection) parameter is enabled only for motor 1.
If motor 2 is selected, V/F control will be given constant torque characteristics.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f170
Base frequency 2
20.0-500.0
*1
f171
Base frequency voltage 2
50-330 (V) (240V class)
50-660 (V) (500V class)
*1
f172
Torque boost value 2
0.0-30.0 (%)
Depending on model
(Refer to section 11.4)
f173
Motor electronic-thermal
protection level 2
10-100 (%) / (A) *2
100
f185
Stall prevention level 2
10-199 (%) / (A),
200 : Disabled *2
150
*1: Default setting values vary depending on the setup menu. Refer to section 11.5.
*2: The inverter's rated current is 100%. When
f701
(current and voltage unit selection)
=
1
(A (amps)/V (volts)) is set, it can be set at A (amps).